Accreditation No. 676 – Victorian Laboratory
Site No. 1499 – ISO/IEC 17025 (2017)
Infrastructure and Asset Integrity
Service
Product
Determinant
Technique
Procedure
Limitations
Evaluation of air control equipment
Air conditioning and ventilation systems
Air flow
Not applicable
- ASHRAE 55
- ASHRAE 70
- ASHRAE 113
- ASHRAE 130
- ISO 5219
- ISO 7730
- AS 4740
- ADC FD72
- ARI 650
- BS 4797 Part 1
Dampers
Cyclic test; Dynamic closure; Leakage; Operation; Temperature degradation
Not applicable
- UL 555
- BS EN 1751
- ISO 10294
- AS 1682.1
- SS 333
Fans
Air delivery; Air flow; Fan speed and power
Not applicable
- Air delivery, fan speed and power of electric circulating fans for household and similar use, excluding ceiling-type fans, to AS 2071-1984
- Air flow measurement of fans and blowers using ASHRAE 51-75 nozzles, pitot tubes
- Air flow measurement of gas fired ducted air heaters using ASHRAE 51-75 nozzles to AS 4556 and AG 106 (M.O.T.5.13.1-96)
- BS 848 Part 1
- ISO 5801
Air flow measurements with least uncertainties of measurement of:
- 6% from 0.01 to 1.0 m³/s using orifice plates;
- 4% from 0.05 to 1.0 m³/s using ASHRAE 51-75 nozzles;
- 10% from 2 to 5 m³/s using pitot tubes;
- 4% from 5 to 50 m³/s using pitot tubes;
- 10% from 0.2 to 2 m³/s using hot-wire anemometers;
- 5% from 2 to 10 m³/s using hot-wire anemometers;
- 20% from 0.2 to 20 m³/s using vane anemometers
Site No. 1499 – ISO/IEC 17025 (2017)
Manufactured Goods
Service
Product
Determinant
Technique
Procedure
Limitations
Acoustic performance evaluation of products
Air conditioners and heat pumps; Air distribution products; Building materials and elements of construction
Sound pressure level
Not applicable
- BS 4718:1971 (Clauses 2.3 and 3 only)
- BS EN ISO 7235 (Clauses 6.2.1, 6.3 and 6.4 only)
- BS 4856 Part 4
- ADC 1062 R4
- ARI 880 (Sound power components only)
- ARI 885 (Sound power components only)
- ARI 890 (Sound power components only)
- ISO 3741:1999 (Broadband Noise measurements only)
- ISO 3741 (Broadband Noise measurements only)
- AS 1217.2:1985
- AS 1277:1983
Static and dynamic insertion loss and generated noise level of air distribution system silencers, fan coil units, unit heaters and unit coolers; ISO 3741 over the frequency ranges:
- 63 Hz to 8 kHz in one third octave bands
- 63 Hz to 8 kHz in octave bands
Mechanical performance evaluation of components for building envelopes, framing and interior lining
Door, window and skylight assemblies
Air infiltration; Deflection; Operating force; Proof load; Strength at ultimate limit state loading; Structural performance evaluation; Water penetration resistance
Cyclic pressure; Static pressure
- AS/NZS 4420.1
- AS 2047 Section 2
Facade assemblies including interior and exterior cladding systems
Air infiltration; Deflection; Proof load; Strength at ultimate limit state loading; Structural performance evaluation; Water penetration resistance
Cyclic pressure; Static pressure
Including on-site tests to:
- AS/NZS 4284 Sections 8.2, 8.3, 8.4, 8.5, 8.6, 8.8 and Appendices C, D, E (CSIRO SIROWET procedure)
- NCC Building Code of Australia (Volume 1, Section FV1 and Volume 2, Section V2.2.1)
Facade assemblies including interior and exterior cladding systems; Wall, floor and ceiling panels
Water penetration resistance
Field check – Spray
Including on-site tests to:
- AAMA 501.2
Site No. 21177 – ISO/IEC 17025 (2017)
Manufactured Goods
Service
Product
Determinant
Technique
Procedure
Limitations
Electrical equipment approval and safety evaluation
Audio, video and similar electronic equipment; Information technology equipment
Electrical safety
Dimensional assessment including creepage and clearance; Electrical characteristics; Energy measurement; Fire hazard assessment; Firmware assessment; Function assessment including abnormal operation; Insulation and electrical protection measurement; Mechanical assessment; Temperature; Visual examination
- AS/NZS 62368.1 (excluding radiation measurements)
- IEC 62368-1
Electrical appliances, coupling devices and accessories; Enclosures for electrical equipment
Electrical safety
Dimensional assessment including creepage and clearance; Electrical characteristics; Endurance and resistance to external conditions; Energy measurement; Fire hazard assessment; Firmware assessment; Function assessment including abnormal operation; Insulation and electrical protection measurement; Mechanical assessment; Temperature; Visual examination
- AS/NZS 3100
- AS/NZS 60335.1 (excluding Clauses 19.11.4; 22.201 and Annexes F; H)
- AS/NZS 60335.2.2
- AS/NZS 60335.2.3
- AS/NZS 60335.2.5
- AS/NZS 60335.2.6
- AS/NZS 60335.2.7
- AS/NZS 60335.2.9
- AS/NZS 60335.2.10
- AS/NZS 60335.2.11
- AS/NZS 60335.2.13
- AS/NZS 60335.2.14
- AS/NZS 60335.2.15
- AS/NZS 60335.2.21
- AS/NZS 60335.2.23
- AS/NZS 60335.2.24
- AS/NZS 60335.2.29
- AS/NZS 60335.2.30
- AS/NZS 60335.2.31
- AS/NZS 60335.2.35
- AS/NZS 60335.2.40
- AS/NZS 60335.2.41
- AS/NZS 60335.2.45
- AS/NZS 60335.2.60
- AS/NZS 60335.2.61
- AS/NZS 60335.2.65 (excluding Clauses 16.101, 22.103, 23.101, 32, Annex AA)
- AS/NZS 60335.2.75
- AS/NZS 60335.2.78
- AS/NZS 60335.2.80
- AS/NZS 60335.2.84
- AS/NZS 60335.2.95
- AS/NZS 60335.2.97
- AS/NZS 60335.2.98
- AS/NZS 60335.2.102
- AS/NZS 60335.2.103
- AS/NZS IEC 60670.1
- IEC 60335-1 (excluding Clause 19.11.4 and Annexes F; H)
- IEC 60335-2-2
- IEC 60335-2-3
- IEC 60335-2-5
- IEC 60335-2-6
- IEC 60335-2-7
- IEC 60335-2-9,
- IEC 60335-2-10
- IEC 60335-2-11
- IEC 60335-2-13
- IEC 60335-2-14
- IEC 60335-2-15
- IEC 60335-2-21
- IEC 60335-2-23
- IEC 60335-2-24
- IEC 60335-2-29
- IEC 60335-2-30
- IEC 60335-2-31
- IEC 60335-2-35
- IEC 60335-2-40
- IEC 60335-2-41
- IEC 60335-2-45
- IEC 60335-2-60
- IEC 60335-2-61
- IEC 60335-2-65 (excluding Clause 16.101, 22.103, 23.101, 32, Annex AA)
- IEC 60335-2-75
- IEC 60335-2-78
- IEC 60335-2-80
- IEC 60335-2-84
- IEC 60335-2-95
- IEC 60335-2-97
- IEC 60335-2-98
- IEC 60335-2-102
- IEC 60335-2-103
- IEC 60670-1
Electrical appliances, coupling devices and accessories; Enclosures for electrical equipment; Laboratory and electromedical equipment
Effect of environmental exposure on electrical equipment and enclosures
Cold; Damp heat; Dry heat; Humidity; Shock (impact); Temperature; Vibration
- AS IEC 60068:2003
- AS IEC 60068.2.1
- AS IEC 60068.2.2
- AS IEC 60068.2.6
- AS IEC 60068.2.27
- AS IEC 60068.2.30
- AS IEC 60068.2.64
- AS IEC 60068.2.78
- Temperature in the range -70ºC to +180ºC;
- Relative humidity in the range 5 to 97% RH between 5ºC and 70ºC
- Vibration – broad band random, sinusoidal and transient (shock)
Electrical appliances, coupling devices and accessories; Power tools – Electric
Degree of protection – IP rating
Not applicable
- AS 60529
- IEC 60529
Electrical cables, cords and conductors; Electrical plugs, sockets, lead assemblies and related components
Electrical performance of electrical cables, cords and conductors; Electrical safety of electrical cables, cords and conductors
Ageing; Bending; Combustion propagation; Compatibility; Conductor resistance; Contaminants; Current; Cutting; Density; Dielectric; Dimensions; Durability of markings; Electrical continuity; Flexing; Heat shock; Heating cycling; High voltage; Hot set; Ignitability; Immersion; Impact; Impulse voltage withstand; Insulation resistance; Load cycle; Mass; Partial discharge; Pressure testing; Sequence impedance; Shrinkage; Spark; Surface leakage; Temperature; Tensile strength; Vertical flame propagation; Voids; Voltage; Volume resistivity; Water absorption; Wrapping
- AS/NZS 3191
- AS/NZS 3808 – excluding the following tests:
- Exudation of plasticizer
- Acid and corrosive gas emission
- Melt flow index
- Carbon black content
- Environmental stress crack resistance
- AS/NZS 5000.1 (Working voltages up to and including 0.6/1 (1.2) kV)
- AS/NZS 5000.2 (Working voltages up to and including 450/750 V)
- AS/NZS 5000.3
- AS/NZS 1125 (excluding clause 2.2)
- AS/NZS 1660.1
- AS/NZS 1660.2.1
- AS/NZS 1660.2.2
- AS/NZS 1660.2.3
- AS/NZS 1660.3
- AS/NZS 1660.4
- AS/NZS 1660.5.6 (2005)
- AS/NZS IEC 60332.1.1
- AS/NZS IEC 60332.1.2
- AS/NZS IEC 60332.1.3
- AS/NZS 3808 – excluding the following tests:
- Exudation of plasticizer
- Acid and corrosive gas emission
- Melt flow index
- Carbon black content
- Environmental stress crack resistance
- AS/NZS 5000.1 (Working voltages up to and including 0.6/1 (1.2) kV)
AS/NZS 5000.2 (Working voltages up to and including 450/750 V) - AS/NZS 1125 (excluding clause 2.2)
- AS/NZS 1125 (excluding clause 2.2)
Electrical plugs, sockets, lead assemblies and related components
Electrical safety
Ball pressure; Dimensional assessment including creepage and clearance; Fire hazard assessment; Glow wire flammability; Needle flame; Proof and comparative tracking index; Temperature; Vertical and horizontal flammability; Visual examination
- AS/NZS 60695.2.10
- AS/NZS 60695.2.11
- AS/NZS 60695.2.12
- AS/NZS 60695.2.13
- AS/NZS 60695.10.2
- AS/NZS 60695.11.5
- AS/NZS 60695.11.10
- AS/NZS 60695.11.20
- AS/NZS 60112
- IEC 60695-2-10
- IEC 60695-2-11
- IEC 60695-2-12
- IEC 60695-2-13
- IEC 60695-10-2
- IEC 60695-11-5
- IEC 60695-11-10
- IEC 60695-11-20
- IEC 60112
Luminaires
Electrical safety
Dimensional assessment including creepage and clearance; Electrical characteristics; Endurance and resistance to external conditions; Energy measurement; Fire hazard assessment; Firmware assessment; Function assessment including abnormal operation; Insulation and electrical protection measurement; Mechanical assessment; Temperature; Visual examination
- AS/NZS 60598.1
- AS/NZS 60598.2.1
- AS/NZS 60598.2.2
- AS/NZS 60598.2.3
- AS/NZS 60598.2.4
- IEC 60598-1
- IEC 60598-2-1
- IEC 60598-2-2
- IEC 60598-2-3
- IEC 60598-2-4
Power tools – Electric
Electrical safety
Dimensional assessment including creepage and clearance; Electrical characteristics; Endurance and resistance to external conditions; Energy measurement; Fire hazard assessment; Firmware assessment; Function assessment including abnormal operation; Insulation and electrical protection measurement; Mechanical assessment; Temperature; Visual examination
- AS/NZS 62841.1
- AS/NZS 62841.2.1
- AS/NZS 62841.2.3
- AS/NZS 62841.2.5
- AS/NZS 62841.2.10
- AS/NZS 62841.2.11
- AS/NZS 62841.4.2
- IEC 62841-1
- IEC 62841-2-1
- IEC 62841-2-3
- IEC 62841-2-5
- IEC 62841-2-10
- IEC 62841-2-11
- IEC 62841-4-2
Electrical safety
Dimensional assessment including creepage and clearance; Electrical characteristics; Endurance and resistance to external conditions; Energy measurement; Fire hazard assessment; Firmware assessment; Function assessment including abnormal operation; Insulation and electrical protection measurement; Mechanical assessment; Temperature; Visual examination
- AS/NZS 60745.1
- AS/NZS 60745.2.1 (2009)
- AS/NZS 60745.2.3 (2011)
- AS/NZS 60745.2.5 (2011)
- AS/NZS 60745.2.11 (2009)
- AS/NZS 60745.2.15 (2010)
- IEC 60745-1 (2006)
- IEC 60745-2-1
- IEC 60745-2-3
- IEC 60745-2-5 (2010)
- IEC 60745-2-11
- IEC 60745-2-15
Evaluation of electrical appliances and devices – Energy efficiency classification
Air conditioners and heat pumps; Heat pumps; Liquid chilling devices
Energy labelling and minimum energy performance standards (MEPS) evaluation
Calculations for energy labelling; Evaluation of test results against stated performance criteria; Visual assessment of marking and other attributes against stated criteria
- AS/NZS 3823.2
- AS/NZS 4776.2
- AS/NZS 4965.2
Clothes dryers; Dishwashers; Washing machines
Energy labelling and minimum energy performance standards (MEPS) evaluation
Calculations for energy labelling; Evaluation of test results against stated performance criteria; Visual assessment of marking and other attributes against stated criteria
- AS/NZS 2007.2
- AS/NZS 2040.2
- AS/NZS 2442.2
Freezers; Refrigerators
Energy labelling and minimum energy performance standards (MEPS) evaluation
Calculations for energy labelling; Evaluation of test results against stated performance criteria; Visual assessment of marking and other attributes against stated criteria
- AS/NZS 4474
- AS/NZS 4474.2:2009
Swimming pool pumps
Energy labelling and minimum energy performance standards (MEPS) evaluation
Calculations for energy labelling; Evaluation of test results against stated performance criteria
- AS 5102.1 (excluding clause 5.9)
Water heaters
Energy labelling and minimum energy performance standards (MEPS) evaluation
Calculations for energy labelling
- AS/NZS 4692.2
Evaluation of electrical appliances and devices – Performance
Air conditioners and heat pumps
Condensate disposal; Dehumidifier capacity; Dehumidifying effectiveness; Enclosure sweat appraisal; Freeze up appraisal; Maximum operating efficiency; Sensible cooling effectiveness; Sensible heating effectiveness; Standby power; Thermal capacity check; Total cooling effectiveness; Volumetric air flow rate
Calorimetric test; Enthalpy
- AS/NZS 3823.1.1
- AS/NZS 3823.1.2
- AS/NZS 3823.1.3
- AS/NZS 3823.1.4
- AS/NZS 3823.1.5
- AS/NZS 3823.4.1
- AS/NZS 3823.4.2
- AS/NZS 3823.4.3
- AS/NZS 4755.3.1
- AS/NZS 4776.1.1
- AS/NZS 4776.1.2
- AS/NZS 4965.1 (Calorimeter and air enthalpy methods only)
- AS/NZS 5125.1
- EN 14511-2
- EN 14511-3
- EN 14511-4
- EN 14825
- ISO 5151
- ISO 13253
- ISO 13256-1
- ISO 15042
- ISO 16358-1
- ISO 16358-2
- ISO 16358-3
- AHRI 1160 (I-P)
- AHRI 1161 (SI)
- AHRI 1230
- ANSI/AHAM DH-1
- AS/NZS 62301
Including liquid chilling packages
Clothes dryers; Dishwashers; Freezers; Refrigerators; Washing machines; Water heaters
Air temperature; Cabinet and chamber volumes; Current; Cycle times; Distribution temperature; Drying effectiveness; Electrical energy consumption; Electrical voltage; Enamel thickness and imperfections; Evaporation efficiency; Ice making capability; Lining solubility; Liquid temperature; Load capacity; Power; Pull down time; Rinsing effectiveness; Standby power; Strength and dimensions of components; Temperature control; Temperature limits in dryers; Vibration; Washing or soil removal; Water consumption; Water extraction effectiveness; Water pressure range; Whiteness retention
Not applicable
- AS/NZS 4474.1:2007
- ISO 8561:1995
- ISO 15502:2005
- IEC 62552-1
- IEC 62552-2
- IEC 62552-3
- AS/NZS IEC 62552-1
- AS/NZS IEC 62552-3
- AS/NZS IEC 62552-3
- AS/NZS 2007.1
- AS/NZS 2040.1
- AS/NZS 2442.1
- AS 1056.1:1991
- AS 3498
- AS/NZS 4692.1
- NZS 4602
- NZS 4606.1
- AS/NZS 60335.2.21
- AS/NZS 62301
AS 3498 Section 7.2, Appendices A, B, C;
AS/NZS 60335.2.21: Clause 22.47 and Annex AA 22.47
Products and appliances connected to the water supply – Physical evaluation
Combination washer/dryers; Dishwashers
Hydrostatic pressure; Rating of products for water efficiency
Not applicable
- AS/NZS 6400
- AS/NZS 4692.1
- AS 1056.1:1991
- AS/NZS 6400 (Sections 2.1, 2.2, 2.3, 2.4, 2.5, 2.6, 2.7, Tables 3.1 and 3.2 only)
- AS/NZS 4692.1 (Clause 2.2.2 only)
- AS 1056.1:1991 (Clause 2.7 only)
Accreditation No. 676 – Traffic Systems
Site No. 15858 – ISO/IEC 17025 (2017)
Calibration
The uncertainty of measurement is reported as an expanded uncertainty having a level of confidence of 95% unless stated otherwise.
Service
Product
Determinant
Technique
Procedure
Limitations
Speed and velocity – Speed measuring devices
Vehicle with digital display
Speed
Direct measurement against a reference standard
- Vipac Method LI8447
Capability
With Calibration and Measurement Capability of –
- in the range 30 to 110 km/h
- 0.5 km/h at speeds of 30 to 45 km/h;
- 0.7 km/h at speeds of 45 to 65 km/h;
- 0.9 km/h at speeds of 65 to 80 km/h;
- 1.2 km/h at speeds of 80 to 110 km/h;
Speed and velocity – Verification of fixed speed detector installations
Inductive loop speed measurement systems; Piezoelectric speed measurement systems; Traffic signal phase systems
Field measurement of AC resistance
Direct electrical measurement
Capability
With Calibration and Measurement Capability of –
- at 1 kHz in the range 0.1 Ω to 200 Ω
- 0.05 Ω or 8.3% of reading, whichever is greater
Field measurement of insulation resistance
Direct electrical measurement
Capability
With Calibration and Measurement Capability of –
- 7.6% of reading in the range from 100 kΩ to 500 MΩ
Field measurement of voltage
Direct electrical measurement
Capability
With Calibration and Measurement Capability of –
- Voltage measuring equipment (picoscope)
- Stored waveforms in the range 10 mV to 20 V
- 5 mV or 5 % of reading, whichever is greater
Field measurement of inductance
Direct electrical measurement
Capability
With Calibration and Measurement Capability of –
- 1 kHz in the range 10 μH to 2 mH
- 0.5 μH or 1.5% of reading, whichever is greater
Field measurement of DC resistance
Direct electrical measurement
Capability
With Calibration and Measurement Capability of –
- 0.05 Ω in the range from 0.1 Ω to 200 Ω
Field measurement of capacitance
Direct electrical measurement
Capability
With Calibration and Measurement Capability of –
- at 1 kHz in the range 0.5 nF to 1 μF
- 0.1 nF or 0.6% of reading, whichever is greater
Accreditation No. 676 – Gas Technology Services
Site No. 669 – ISO/IEC 17025 (2017)
Calibration
The uncertainty of measurement is reported as an expanded uncertainty having a level of confidence of 95% unless stated otherwise.
Service
Product
Determinant
Technique
Procedure
Limitations
Chemical metrology – Gas analysers
Gas analysers
Concentration
Direct measurement by certified reference material
- In-house method WI-UIN-66
- Carbon monoxide: (electrochemical) 0 – 0.1% (v/v)
- Oxygen: (electrochemical) 0 – 25% (v/v)
- Methane (thermal conductivity): 0 – 100% (v/v)
- Methane (hot wire): 0 – 100% (v/v)
- Methane (catalytic combustion): 0 – 100% (v/v)
- CH4 (semiconductor): 0 – 0.05% (v/v)
- Methane (infra-red): 0 – 100% (v/v)
- Propane (thermal conductivity): 0 – 0.1% (v/v)
- Propane (hot wire): 0 – 100% (v/v)
- Propane (catalytic combustion): 0 – 100% (v/v)
- Propane (semiconductor): 0 – 0.1% (v/v)
- Propane (infrared): 0 – 100% (v/v)
- Hydrogen sulfide (electrochemical): 0 – 0.01% (v/v)
- Natural gas (thermal conductivity): 0-100% (v/v)
Capability
With Calibration and Measurement Capability of –
- Carbon monoxide: Electrochemical: 5% relative or 0.0006% (v/v) over the range 0 – 0.1% (v/v), whichever is greater
- Oxygen: Electrochemical: 2.5% relative or 0.2% (v/v) over the range 0 – 25% (v/v), whichever is greater
- Methane: Thermal conductivity: 3% (v/v) over the range 0 – 100% (v/v)
- Methane: Hot wire: 2% LEL over the range 0 – 100% LEL
- Methane: Catalytic combustion: 2% LEL over the range 0 – 100% LEL
- Methane: Semiconductor: 5% relative or 0.0005% (v/v) (whichever is larger) in the range 0 – 0.05% (v/v) and 5% relative in the range 0.05% – 0.1% (v/v)
- Methane: Infrared: 2% (v/v) from 0 – 100% (v/v)
- Propane: Thermal conductivity: 2.5% relative or 0.0005% (v/v) over the range 0 – 0.1% (v/v)
- Propane: Hot wire: 2% LEL over the range 0 – 100% LEL
- Propane: Catalytic combustion: 2% LEL over the range 0 – 100% LEL
- Propane: Semiconductor: 5% relative or 0.0005% (v/v) (whichever is larger) in the range 0-0.05% (v/v) and 5% relative in the range 0.05% to 0.1% (v/v)
- Propane: Infrared: 2% (v/v) from 0 – 100% (v/v)
- Hydrogen sulfide : Electrochemical: 5% relative or 0.0003% (v/v) over the range 0 – 0.01% (v/v), whichever is greater
- Natural gas: Thermal conductivity: 3% (v/v) gas/methane over the range 0-100% (v/v) gas/methane
Flow metrology – Flow measuring devices and systems
Coriolis meters; Gas meters; Orifice meters
Volume (and nominal flow rate)
Volumetric transfer
Gaseous flow in the flow rate range of 2 mL/h to 3000 m³/h
Capability
With Calibration and Measurement Capability of –
- Gaseous flow in the flow rate range of 2 mL/h to 1000 m³/h
- the greater of: 0.18% of flow rate or 2 mL/h, with a minimum test volume of 1 mL;
- Gaseous flow In the flow rate range of 1000 m³/h to 2000 m³/h
- 0.21% of flow rate, with a minimum test volume of 10 L;
- Gaseous flow in the flow rate range of 2000 m³/h to 3000 m³/h
- 0.26% of flow rate, with a minimum test volume of 10 L
Flow computers
Volume (and nominal flow rate)
Comparison with a reference meter
- In-house procedures WI-IN-008 and WI-IN-010
Capability
With Calibration and Measurement Capability of –
- 0.12% of volume, with a minimum test volume of 2 L
Gaseous volume proving systems; Oil and gas measurement systems
Volume (and nominal flow rate)
Volumetric transfer
2 L to 200 kL
Capability
With Calibration and Measurement Capability of –
- 0.1% of volume, with a minimum test volume of 2 L
Sonic nozzles
Flow rate
Volumetric transfer
Gaseous flow in the flow rate range up to 500 m³/h
Capability
With Calibration and Measurement Capability of –
- The greater of: 0.18% of flow rate or 2 mL/h, with a minimum test volume of 1 mL
Pressure metrology – Pressure and vacuum measuring equipment
Barometers
Absolute pressure
Comparison with reference instrument
80 kPa to 105 kPa
Capability
With Calibration and Measurement Capability of –
- 7 Pa from 80 kPa to 105 kPa
Digital pressure gauges; Manometers; Mechanical pressure gauges; Pressure recorders; Pressure transducers; Vacuum gauges
Absolute pressure; Gauge pressure
Comparison with reference instrument
- AS 1349
Capability
With Calibration and Measurement Capability of –
- Gauge pressure
- 0.01% or 1 Pa (whichever is greater) from -95 kPa to -1.7 kPa
- 0.5 Pa from -1.7 kPa to 1.7 kPa;
- 0.01% or 1 Pa (whichever is greater) from 1.7 kPa to 14 MPa
- Absolute pressure
- 0.01% or 2 Pa (whichever is greater) from 5 kPa to 14 MPa
Temperature metrology – Temperature measuring equipment
Digital temperature measuring systems
Temperature
Measurement against reference standard
Capability
Integral thermometers in Flow Computers
with Calibration and Measurement Capability of –
- 0.5°C in the range 10°C to 30°C